SUNNY CENTRAL 250U/500U

Perfect for commercial systems in North America
 
The two proven central inverters are ideally suitable for commercial plants in North America: The integrated transformer makes possible direct connection with the low-voltage grid and, thanks to the outdoor enclosure with the OptiCool cooling concept, the devices can be installed practically anywhere. The leading edge efficiency of 97.5 %, which is remarkable for transformer devices, is just as convincing as the simple monitoring and remote maintenance via the integrated data logger – optionally with RS485, Ethernet or OPC interface. Special highlight: when others switch off, the two Sunny Central inverters continue to feed at a lower output. This means that in the temperature range of 122 to 140 °F (50 to 60 °C), up to 75 % of the nominal output is still available.

Efficiency     

  • 97.5 % leading edge efficiency     
  • Direct connection to the  480 V grid     
  • Suitable for ambient temperatures of up to 140 °F / 60 °C


Reliable     

  • Galvanic isolation      
  • Weatherproof enclosure     
  • Integrated data logger      
  • Simple remote query and maintenance per remote access


Strong peripherals     

  • AC/DC disconnect unit     
  • Circuit combiner boxes for sting collection     
  • Sunny Central String-Monitor US
  Sunny Central 250-US Sunny Central 500-US
Input data    
Max. DC power 285 kWp 1) 570 kWp 1)
MPP voltage range 330 V – 600 V 330 V – 600 V
Max. DC voltage 600 V 600 V
Feed starting at [U]/[P] 380 V / 5000 W 380 V / 5000 W
Max. DC current 800 A 1600 A
Number of DC inputs 4 – 6 6 – 9
     
Output data    
Nominal AC power 250 kVA @ 45 °C 500 kVA @ 45 °C
Max. AC current 300 A @ 480 V 600 A @ 480 V
AC grid frequency 60 Hz 60 Hz
AC voltage range 422 V – 528 V 422 V – 528 V
AC voltage range, full active power 480 V – 514 V 480 V – 514 V
Power factor (cos φ) > 0.99 > 0.99
Max. THD < 3 % < 3 %
     
Efficiency 2)    
Max. efficiency 97.50 % 97.40 %
CEC efficiency 97.00 % 97.00 %
Euro-eta 96.60 % 96.90 %
     
Ambient conditions    
Operating temperature range –25 °C … +50 °C / –13 °F ... +122 °F –25 °C … +50 °C / –13 °F ... +122 °F
Max. temperature for nominal conditions +45 °C / +113 °F +45 °C / +113 °F
Protection rating NEMA 3R NEMA 3R
Installation indoors / outdoors yes / yes yes / yes
Rel. humidity 15 % … 95 % 15 % … 95 %
Fresh air consumption 4000 m3/h 6000 m3/h
Internal consumption at nominal power < 800 W < 1500 W
Standby consumption (Pnight) < 69 W < 80 W
     
Dimensions and weight    
Height 2027 mm (80 in) 2027 mm (80 in)
Width 2786 mm (110 in) 3536 mm (140 in)
Depth 830 mm (33 in) 930 mm (37 in)
Weight < 1900 kg / 4189 lb < 3250 kg / 7165 lb
     
Certificates / listings    
Certificates UL 1741, UL 1998, IEEE 1547 UL 1741, UL 1998, IEEE 1547
EMC conformity FCC, Part 15, Class A FCC, Part 15, Class A
     
Interfaces    
RS485 / Ethernet / Analog opt. / opt. / opt. opt. / opt. / opt.
Display: text line / graphic yes /— yes /—
Communication protocols Modbus / TCP Modbus / TCP
SSM-US connection RS485 RS485
Plant monitoring Sunny Portal Sunny Portal
     
1) Specifications apply to irradiation values below STC
2) Measured without an internal power supply at UDC = 325 V (SC 250U) or 330 V (SC 500U)
   
     
Type designation SC 250U SC 500U

Downloads

Language:
Data sheet


284 KB

SUNNY CENTRAL 250U / 500U - The ideal inverter for large scale PV power systems
Type: Data sheet
Language: English (US)
Document number: SC250SC500-DUS095022
Version number: 2.2


180 KB

Monitoring Solutions - Accurate revenue grade metering & data communication
Type: Data sheet
Language: English (US)
Document number: POWERMEAS-HUS093016
Version number: 1.6
User Manual


1.549 KB

SUNNY CENTRAL 250U / 500U / 500HE-US - User Manual
Type: User Manual
Language: English (US)
Document number: SCUS-BUS094812
Version number: 1.2
Installation Guide


9.121 KB

SUNNY CENTRAL 500U - Installation Guide
Type: Installation Guide
Language: English (US)
Document number: SC500U-IUS093411
Version number: 1.1


3.161 KB

SUNNY CENTRAL 250U - Installation Guide
Type: Installation Guide
Language: English (US)
Document number: SC250U-IUS093413
Version number: 1.3


1.507 KB

SUNNY CENTRAL 250U - Installation Guide / Change from negative to positive grounding
Type: Installation Guide
Language: English (US)
Document number: SC250U_GFDI-IUS101711
Version number: 1.1


1.213 KB

SUNNY CENTRAL 500U - Installation Guide / Change from negative to positive grounding
Type: Installation Guide
Language: English (US)
Document number: SC500U_GFDI-IUS101311
Version number: 1.1
Technical information


1.763 KB

Installation requirements for SUNNY CENTRAL 250U
Type: Technical information
Language: English (US)
Document number: SC250U-Auf-UUS091211
Version number: 1.0


1.467 KB

Installation requirements for SUNNY CENTRAL 500U
Type: Technical information
Language: English (US)
Document number: SC500U-Auf-UUS092911
Version number: 1.1
Certificate


75 KB

Certificate of Compliance - SUNNY CENTRAL 500U
Type: Certificate
Language: English (US)
Document number: SC500U-US-ZEN103410
Version number: 1.0


63 KB

Certificate of Compliance - SUNNY CENTRAL 250U
Type: Certificate
Language: English (US)
Document number: SC250U-US-ZEN103410
Version number: 1.0
Promotion Material


286 KB

INVERTER GUIDE
Type: Promotion Material
Language: English (US)
Document number: INVERTER_POSTER102808
Version number: