SUNNY ISLAND 5048 / 5048US

The Island Manager

Commissioning within minutes: the Sunny Island 5048 makes it possible. All required operational settings can be made quickly and easily in just a few steps. The Sunny Island 5048 is flexible in its application, extendable and takes on all control processes. Its first-class battery management ensures maximum battery life. In addition, the device features an impressive high-efficiency, ergonomic die-cast aluminum enclosure and an OptiCool active cooling system. The Sunny Island is also available in a UL-compliant 5048-US version with an output rating of 120 V and 60 Hz for the North American market.

Flexible

  • For systems from 3 to 300 kW
  • 1- and 3-phase operation, connectable in parallel and modularly extendable
  • AC and DC coupling


Simple

  • Easy commissioning with the "Quick Configuration Guide"
  • Complete off-grid management



Efficient

  • High efficiency
  • Intelligent battery management for maximum battery life
  • Charge level calculation


Robust

  • Extreme overload capability
  • OptiCool
  • 5-year SMA warranty
  Sunny Island 5048 Sunny Island 5048-US
AC output (loads)    
Nominal AC voltage (adjustable) 230 V (202 V – 253 V) 120 V (105 V – 132 V)
Nominal frequency (adjustable) 50 Hz / 60 Hz (45 Hz – 65 Hz) 60 Hz (55 Hz – 65 Hz)
Continuous AC power at 25 °C / 45 °C 5000 W / 4000 W 5000 W / 4000 W
AC output power at 25 °C for 30 min / 1 min / 3 s 6500 W / 8400 W / 12000 W 6500 W / 8400 W / 11000 W
Nominal AC current / max. AC current (peak) 21.7 A / 120 A for 60 ms 41.7 A /180 A for 60 ms
THD output voltage / power factor (cos φ) < 3 % / –1 to +1 < 3 % / –1 to +1
     
AC input (generator or grid)    
AC input voltage (range) 230 V (172.5 V – 264.5 V) 120 V (80 V – 150 V)
AC input frequency (range) 50 Hz / 60 Hz (40 Hz – 70 Hz) 60 Hz (54 Hz – 66 Hz)
Max. input current (adjustable) / max. input power 56 A (0 A – 56 A) / 12.8 kW 56 A (0 A – 56 A) / 6.7 kW
     
Battery DC input    
Battery voltage (range) 48 V (41 V – 63 V) 48 V (41 V – 63 V)
Max. battery charging current / continuous charging current at 25 °C 120 A / 100 A 120 A / 100 A
Battery type / battery capacity (range) lead, NiCd / 100 – 10,000 Ah lead, NiCd / 100 – 10,000 Ah
Charge control IUoU process IUoU process
     
Efficiency / operating consumption    
Max. efficiency 95 % 95 %
Own consumption with no load / standby 25 W / 4 W 25 W / 4 W
     
Protection devices    
DC reverse polarity protection / DC fuse yes / yes yes / yes
AC short-circuit / AC overload yes / yes yes / yes
Overtemperature / excessive battery discharge yes / yes yes / yes
     
General data    
Dimensions (W / H / D) in mm 467 / 612 / 235 467 / 612 / 235
Weight 63 kg 63 kg
Operating temperature range –25 °C ... +50 °C –25 °C ... +50 °C
Protection rating (as per IEC 60529) indoors (IP30) indoors (NEMA 1)
     
Features / function    
Operation & display / multifunction relays internal / 2 internal / 2
3-phase systems / parallel connection yes / yes yes / yes
Integrated bypass / multicluster operation — / yes — / yes
Charge level calculation / full- / equalization charge yes / yes / yes yes / yes / yes
Integrated soft start / generator support yes / yes yes / yes
Battery temperature sensor / communication cables yes / yes yes / yes
Warranty: (5 / 10 / 15 / 20 / 25 years) yes / opt. / opt. / opt. / opt. yes / opt. / opt. / opt. / opt.
Certificates and permits www.SMA-Solar.com www.SMA-Solar.com
     
Accessories    
Battery cables / battery fuses opt. / opt. opt. / opt.
Interfaces (RS485 / Multicluster PB) opt. / opt. opt. / opt.
GenMan extended generator start opt. opt.
Load-shedding contactor / battery current measurement opt. / opt. opt. / opt.
     
Last revision: May 2010    
Type designation SI 5048 SI 5048U
     

Downloads

Language:
Data sheet


851 KB

SUNNY ISLAND 5048U - Battery-based inverter for off-grid and back-up applications
Type: Data sheet
Language: English (US)
Document number: SUNNYISL5048U-DUS101215
Version number: 1.5
Technical Description


7.853 KB

SUNNY ISLAND 5048U - Technical Description for SUNNY ISLAND Firmware Version 5.0
Type: Technical Description
Language: English (US)
Document number: SI5048U-TUS094330
Version number: 3.0


5.741 KB

SUNNY ISLAND 5048U - Installation & Instruction Manual for SUNNY ISLAND Firmware Version 2.0
Type: Technical Description
Language: English (US)
Document number: SI5048U-TUS091012
Version number: 1.2
Certificate


68 KB

UL-Notice of Authorization to apply the UL Mark - Sunny Island 5048U
Type: Certificate
Language: English (US)
Document number: UL_SI5048U