SUNNY CENTRAL CP-US CoMVPP 1,0 MW

COMPACT MEDIUM VOLTAGE POWER PLATFORM

Simplified solution means maximum ROI for utility-scale projects

The Compact MV Power Platform is a turnkey power conversion solution for utility-scale PV plants. Designed for use with the Sunny Central CP-US and the Sunny Central CP XT central inverter lines, this solution minimizes risk and maximizes energy production, providing 110 percent power output at temperatures up to 25 ºC. The Compact MV Power Platform is engineered for maximum ROI, offering reduced system costs, high reliability and best-in-class system efficiencies above 97 percent. Simple installation, easy data monitoring and superior service offerings make the Compact MV Power Platform the preferred choice for large scale projects in North America.

Reduced LCOE

  • Reduced balance of system costs with 1000 VDC design
  • Auxiliary HVAC not required, even in desert environments
  • Factory-integrated grid management, including reactive power control and LVRT

Efficient

  • Best-in-class system effi ciencies above 97 % peak
  • 10 % additional power for continuous operation at ambient temperatures up to 25 °C
  • Low loss transformer engineered for PV application 

Certified

  • Rigorous environmental testing
  • NRTL listing of entire platform
  • NEC 2011 compliant 

Turnkey

  • Simplifi ed shipping and installation process
  • Extensive service offerings and O&M support
  • Integrated AC disconnects, optional DC disconnects and various confi guration options
Show All / Hide All SUNNY CENTRAL CP-US CoMVPP 1,0 MW SUNNY CENTRAL CP-US CoMVPP 1,25 MW SUNNY CENTRAL CP-US CoMVPP 1,44 MW SUNNY CENTRAL CP-US CoMVPP 1,5 MW SUNNY CENTRAL CP-US CoMVPP 1,6 MW
Input (DC)
MPP voltage range at 25 °C (77 °F) / at 50 °C (122 °F) at 60Hz 430 V … 820 V / 430 V … 820 V2 500 V … 820 V / 2 525 V … 820 V2 545 V … 820 V / 545 V … 820 V2 570 V … 820 V / 570 V … 820 V2
Max. DC voltage 1000 V 1000 V 1000 V 1000 V 1000 V
Max. DC input current 2500 A 2700 A 3200 A 3200 A 3200 A
Number of independent MPP inputs 2 2 2 2 2
Number of fused DC inputs 18 18 18 18 18
Output (AC)
Nominal AC power 1000 kVA @ 50 °C (122 °F) 1260 kVA @ 50 °C (122 °F) 1440 kVA @ 50 °C (122 °F) 1500 kVA @ 50 °C (122 °F) 1600 kVA @ 50 °C (122 °F)
Maximum AC power 1100 kVA @ 25 °C (77 °F) 1400 kVA @ 25 °C (77 °F) 1584 kVA @ 25 °C (77 °F) 1650 kVA @ 25 °C (77 °F) 1760 kVA @ 25 °C (77 °F)
Nominal AC voltage options 12,47 kV; 13,8 kV; 20,6 kV; 24,9 kV; 27,6 kV; 34,5 kV 12,47 kV; 13,8 kV; 20,6 kV; 24,9 kV; 27,6 kV; 34,5 kV 12,47 kV; 13,8 kV; 20,6 kV; 24,9 kV; 27,6 kV; 34,5 kV 12,47 kV; 13,8 kV; 20,6 kV; 24,9 kV; 27,6 kV; 34,5 kV 12,47 kV; 13,8 kV; 20,6 kV; 24,9 kV; 27,6 kV; 34,5 kV
Grid frequency 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
Power factor (adjustable) 0.8 leading ... 0.8 lagging 0.8 leading ... 0.8 lagging 0.8 leading ... 0.8 lagging 0.8 leading ... 0.8 lagging 0.8 leading ... 0.8 lagging
Transformer vector group Dy1y1 Dy1y1 Dy1y1 Dy1y1 Dy1y1
Transformer no load taps ±2,5 % & ±5,0 % ±2,5 % & ±5,0 % -5,0 %; -2,5 %; +2,5 %; +5,0 %; +7,5 %; +10,0 % -5,0 %; -2,5 %; +2,5 %; +5,0 %; +7,5 %; +10,0 % -5,0 %; -2,5 %; +2,5 %; +5,0 %; +7,5 %; +10,0 %
Transformer cooling type KNAN KNAN KNAN KNAN KNAN
Power consumption
Internal consumption in operation (inverter + MV-transformer) 4 < 3800 VA + < 10,1 kVA < 3800 VA + < 12,4 kVA < 3800 VA + < 14,6 kVA < 3800 VA + < 14,6 kVA < 3800 VA + < 15,7 kVA
Standby consumption (inverter + MV-transformer) < 300 VA + < 1100 VA < 300 VA + < 1350 VA < 300 VA + < 1600 VA < 300 VA + < 1600 VA < 300 VA + < 1700 VA
Integrated control power supply / external control power supply yes / opt. yes / opt. yes / opt. yes / opt. yes / opt.
External auxiliary supply voltage 480 V; 600 V 480 V; 600 V 480 V; 600 V 480 V; 600 V 480 V; 600 V
Efficiency
Max. efficiency / CEC efficiency inverter 98,10 % / 97,50 % 98,50 % / 98,00 % 98,60 % / 98,00 % 98,60 % / 98,00 % 98,70 % / 98,50 %
MVPP System Efficiency Peak > 97 % > 97,5 % > 97,5 % > 97,5 % > 97,5 %
Protection rating and ambient conditions
Protection rating NEMA 3R NEMA 3R NEMA 3R NEMA 3R NEMA 3R
Operation temperature range @ nominal power -25 °C (-13 °F) ... 50 °C (+122 °F) -25 °C (-13 °F) ... 50 °C (+122 °F) -25 °C (-13 °F) ... 50 °C (+122 °F) -25 °C (-13 °F) ... 50 °C (+122 °F) -25 °C (-13 °F) ... 50 °C (+122 °F)
Storage temperature standard / low temperature option (@Pnom) -25 °C (-13 °F ) ... 60 °C (+140 °F) / -40 °C (-40 °F) ... 60 °C (+140 °F) -25 °C (-13 °F ) ... 60 °C (+140 °F) / -40 °C (-40 °F) ... 60 °C (+140 °F) -25 °C (-13 °F ) ... 60 °C (+140 °F) / -40 °C (-40 °F) ... 60 °C (+140 °F) -25 °C (-13 °F ) ... 60 °C (+140 °F) / -40 °C (-40 °F) ... 60 °C (+140 °F) -25 °C (-13 °F ) ... 60 °C (+140 °F) / -40 °C (-40 °F) ... 60 °C (+140 °F)
Relative humidity 15 % ... 95 % 15 % ... 95 % 15 % ... 95 % 15 % ... 95 % 15 % ... 95 %
Snow load, maximum (psf) 40 40 40 40 40
Wind load, maximum (mph) 110 110 110 110 110
Fresh air consumption (CFM) 3532 3532 3532 3532 3532
Max. altitude above MSL 6562 6562 6562 6562 6562
Design lifetime (years) > 20 > 20 > 20 > 20 > 20
Compliance and Certificates
Seismic rating according UBC sec. 1632 and IBC sec. 16135 Site class D, Ss =2.25g, S1=1.24g Site class D, Ss =2.25g, S1=1.24g Site class D, Ss =2.25g, S1=1.24g Site class D, Ss =2.25g, S1=1.24g Site class D, Ss =2.25g, S1=1.24g
NEC 2011 / OSHA 1910 yes / yes yes / yes yes / yes yes / yes yes / yes
NRTL Listing: UL1741, UL857, UL891, NFPA79 yes yes yes yes yes
PE stamped Structural Calculations yes yes yes yes yes
Features
DC Disconnect Unit / AC Disconnect opt. / yes opt. / yes opt. / yes opt. / yes opt. / yes
Tracker Motor Supply (10kVA@460VAC / 10kVA@480VAC / 20kVA@480VAC / 30kVA@480VAC) opt. / opt. / opt. / opt. opt. / opt. / opt. / opt. opt. / opt. / opt. / opt. opt. / opt. / opt. / opt. opt. / opt. / opt. / opt.
Auxiliary Services Power (none / 2kVA / 7.5kVA) yes / opt. / opt. yes / opt. / opt. yes / opt. / opt. yes / opt. / opt. yes / opt. / opt.
Customer SCADA system Accommodation 864 / 762 / 305 mm (34 / 30 / 12 inch), supply: 120 V / 60 Hz / max. 250 W 864 / 762 / 305 mm (34 / 30 / 12 inch), supply: 120 V / 60 Hz / max. 250 W 864 / 762 / 305 mm (34 / 30 / 12 inch), supply: 120 V / 60 Hz / max. 250 W 864 / 762 / 305 mm (34 / 30 / 12 inch), supply: 120 V / 60 Hz / max. 250 W 864 / 762 / 305 mm (34 / 30 / 12 inch), supply: 120 V / 60 Hz / max. 250 W
Convenience Receptacles 2 x 120 V / max. 250 W each 2 x 120 V / max. 250 W each 2 x 120 V / max. 250 W each 2 x 120 V / max. 250 W each 2 x 120 V / max. 250 W each
Transformer alarm contacts: (Temp / Pressure / Liquid level / Analog Temp) yes / opt. / opt. /opt. yes / opt. / opt. /opt. yes / opt. / opt. /opt. yes / opt. / opt. /opt. yes / opt. / opt. /opt.
Transformer oil containment opt. opt. opt. opt. opt.
Monitoring (extended I/O): 4 DI, 3 AI opt. opt. opt. opt. opt.
Delivery Terms: FCA-Origin yes yes yes yes yes
Platform design
W / H / D (Platform including External Disconnect Units) 9296 / 2591 / 2591 mm (366 / 102 / 102 inch) 9296 / 2591 / 2591 mm (366 / 102 / 102 inch) 9296 / 2591 / 2591 mm (366 / 102 / 102 inch) 9296 / 2591 / 2591 mm (366 / 102 / 102 inch) 9296 / 2591 / 2591 mm (366 / 102 / 102 inch)
Weight (Platform including External Disconnect Units) < 17690 kg (< 39000 lb) < 17690 kg (< 39000 lb) < 17690 kg (< 39000 lb) < 17690 kg (< 39000 lb) < 17690 kg (< 39000 lb)
W / H / D (Platform excluding External Disconnect Units) 7696 / 2591 / 2591 mm (303 / 102 / 102 inch) 7696 / 2591 / 2591 mm (303 / 102 / 102 inch) 7696 / 2591 / 2591 mm (303 / 102 / 102 inch) 7696 / 2591 / 2591 mm (303 / 102 / 102 inch) 7696 / 2591 / 2591 mm (303 / 102 / 102 inch)
Weight (Platform excluding External Disconnect Units) < 15876 kg (< 35000 lb) < 15876 kg (< 35000 lb) < 15876 kg (< 35000 lb) < 15876 kg (< 35000 lb) < 15876 kg (< 35000 lb)
Type designation
Type designation MVPP 1.0 MW MVPP 1.25 MW MVPP 1.44 MW MVPP 1.5 MW MVPP 1.6 MW
Footnote
1) @ 1.05 UAC, nom and cos ϕ = 1
2) @ 1.00 UAC, nom and cos ϕ = 1
3) Standard: 1000 V DC, optional 1100 V DC with a start-up < 1000 V DC
4) Not including platform auxiliary service loads
5) Pier height 3 ft max.